There are two types of wind retransmitters used in the
field. The magnetic amplifier type is powered by two mercury cells and has
no provision for testing wind direction. A newer type is powered by
alternating current (AC) and does have a switch for testing the wind
direction indicator.
At least once a week, the observer should check to
determine that the retransmitter is within the tolerances shown below.
This is done as follows:
a. Advise each office having a wind
indicator drop from the retransmitter that a test is being made.
b. Depress the "TEST"
button on the retransmitter panel.
c. With the "TEST" button
depressed, check the value on the master wind speed indicator. This
value should be within 1 knot of the calibrated speed at
600 RPM.
d. If the master indicator is not
within tolerance and:
(1) You have a magnetic amplifier
type retransmitter, replace the two mercury cells, observing correct
polarity. (If the meter is still out of tolerances, the electronic
technician shall be notified.)
(2) If the station has an AC
powered instrument, corrective maintenance should only be done by the
electronic technician.
e. When the master meter is within
tolerance, make a quick check of all other wind speed meters connected
to the retransmitter. Each meter should be within 1 1/2 knots
of the master meter and should show about the same differences in
subsequent checks. To compare weekly checks keep a record of the
readings from each meter. A sample record is shown in Figure 17-13, Wind
Speed Comparison Data.
Figure 17-13. Wind Speed Comparison Data